SOP 04 · Heating Safety Inspection visit

HVAC SOPs · Version 1 · 1 Oct 2026
← All SOPs

Who: HVAC technicians.
Report: Heating Safety Inspection (Hub → Tools → Field Reports). See SOP 02.
Price and time: $59 per system, 30 minutes. Gas furnace or heat pump.

What it is, and what it isn't

  • It is a safety inspection of the heating system: check, test, measure and photograph. Do the checks that apply to the equipment installed.
  • It changes the filter when the customer provides one.
  • It isn't cleaning: no cleaning, lubricating or adjusting.
  • No gas pressure measurement and no carbon monoxide test. No Delta visit includes either one. Don't offer them, and don't say we did them.
  • On a gas furnace, look only at the parts you can see without taking the furnace apart.

On site, in this order

  1. Thermostat calls for heat.
  2. Startup, heating cycle and shutdown.
  3. Equipment condition and accessible wiring.
  4. Filter condition and fit. Change it if the customer provides one.
  5. Blower wheel and compartment.
  6. Blower motor electrical draw, where accessible.
  7. Supply and return air temperatures.
  8. Airflow: obvious restrictions.
  9. Accessible safety controls: test them without bypassing them.
  10. Auxiliary or emergency heat, if installed.
  11. Heat pump: reversing valve operation.
  12. Heat pump: defrost operation or diagnostic history, as conditions allow.
  13. Heat pump: outdoor coil and fan.
  14. Gas furnace: check the accessible gas connections for leaks.
  15. Gas furnace: gas shutoff condition and access.
  16. Gas furnace: burners, ignition and flame sensing.
  17. Gas furnace: accessible heat-exchanger surfaces, for visible damage.
  18. Gas furnace: accessible venting, and draft where it applies.
  19. Thermostat staging: the system responds to each stage.

Readings the report needs

  • Return and supply temperatures. The form works out the temperature rise; enter the data-plate rise range.
  • Blower motor amps, with the data-plate FLA.
  • Strip amps, if there's electric heat.
  • Gas leak check result, and the method you used.
  • Draft: confirmed, or not checked with the reason.
  • Flame sensor signal (µA): optional, with the maker's minimum if you know it.

Put every other reading in Field data.

Photos

  • Every system:
    • data plates
    • filter
    • blower
    • thermostat
  • Gas furnace:
    • burners and flame
    • flame sensor
    • the heat-exchanger view
    • venting
    • gas shutoff
  • Heat pump:
    • outdoor unit and coil
  • Every yellow and red item

Red or yellow?

Red:

  • a gas leak at a connection;
  • visible damage on an accessible heat-exchanger surface;
  • scorch marks or other signs of flame rollout;
  • disconnected or damaged venting;
  • a safety control that fails its test;
  • overheated wiring;
  • no heat.

Yellow at most:

  • a dirty filter, blower wheel or burners;
  • a dirty flame sensor, or a low signal while the furnace still runs;
  • a dirty outdoor coil on a heat pump;
  • surface rust with no damage.

If you find a gas leak, make it safe first, as you're trained to. The report comes second.

Verdict (pick one)

  • "Working well. No maintenance needed today."
  • "Heating Maintenance is due: [what you saw, one line]."
  • "Needs a repair: [what]." Tick "Heating Maintenance is also due" if it is.

Options and what to say

The report shows these options:

  • Nothing more today: $0.
  • Heating Maintenance: $179 per system. Today's $59 counts toward it within 30 days. It adds cleaning the burners and flame sensor on a gas furnace, or rinsing the outdoor coil on a heat pump.
  • The Safeguard Plan: today's $59 comes off their bill. You do this season's maintenance while you're there, or book the first open slot.

Say it with SOP 11, section 1.

If they join today

Same steps as SOP 03, using the season's plan visit (Heating Maintenance in the fall). Then follow SOP 11, "If they join".

SOP 04 · Version 1 · 1 Oct 2026. If an SOP and the Plan Sheet ever disagree, the Plan Sheet wins. Tell the office.